Emission factor from EPD Ireland EPD, product-specific
ProAir Heat Recovery Ventilation Unit: ProAir PA600LI/ PA600PLI
Ireland · Cradle to grave · Reference year 2022
Each unit of this product counts as 4,139 kg CO₂e over the modules its EPD declares: 3,114 in use (B4, B6) and 1,025 for cradle to grave, embodied.
Value per unit, over the modules the EPD declares
4,139kgCO₂e/unit
EN 15804 modules B4 to B6 · Fossil only · GWP100 · AR5
Derived by open-climate.ai: the sum of EPD Ireland's published parts
The one scenario this EPD declaresReference year 2022
- Region
- Ireland IE
- Boundary
- Cradle to grave
- Data quality
- HighRated by us, not by the source
- Licence
- Open · EPD Ireland terms
- Declared by
- ProAir Heat Recovery Ventilation Systems Ltd. T/A ProAir Systems
Where 4,139 comes from
- Cradle to grave, embodiedDerived by open-climate.aiScope 3, cat. 2, 4 and 51,02524.8%
- B4 ReplacementScope 3, cat. 241.41%
- Scope 1 Scope 2 Scope 3, cat. 33,07374.2%
- Outside the scopes−257beside
Σ 4,139: the three declared modules add up to the total. D stays beside it.
Reporting this item under the GHG Protocol
This period
Scope 3, categories 2 and 4 1,025
This one figure covers both together; no split between them is given.
The product becomes part of a building you own. The product and its installation go to category 2 in the year you buy it, the delivery to category 4. Use and end of life are reported in the years they happen.
Later, when it happens
During use, in the years the building stands
- B4 Scope 3, category 2 41.4
- B6 Scope 1 Scope 2 Scope 3, category 3 3,073
At end of life, in the year of demolition
- Cradle to grave, embodied Scope 3, category 5 1,025
Outside the scopes, reported separately
- D −257
A1-A3 to A5, B1 to B3, B5, B7 and C1 to C4 are not declared: nothing to report.
The factor, standardised
Every factor on open-climate.ai answers the same questions in the same words, whatever the publisher. Open any ⓘ for the definition.
Manufactured goods › Machinery · Ireland · per item · Supplier-specific
Cradle to grave · Fossil only · AR5
- BoundaryCradle to graveFull life cycle: cradle_to_gate plus distribution, use phase and end-of-life. Learn more
- Cradle to grave
- Raw materials, inbound transport, fuel supply, fuel combustion, manufacturing, packaging, purchased energy, installation, outbound transport, use, maintenance and end of life
- GWP methodWhich IPCC assessment report's warming potentials convert each gas to CO₂e, and over how many years the warming is counted (GWP100: 100 years). Learn more
- IPCC AR5, 100-year horizon
- Not on the record; set from EPD Ireland's method notes · impact method EF 3.0
- CO₂e basisWhich carbon the CO₂e counts. Fossil only leaves out biogenic CO₂ and land use; net total counts every pool, net of removals. The same activity on two bases is two different numbers. Learn more
- Fossil only
- Split by carbon origin, not by gas
- Life cycle
- Upstream: coveredProduction: coveredDownstream: coveredEnd of life: covered
High quality · Open licence · Any year
Module by module, up to the total
Seventeen EN 15804 modules, always in the same order. Each declared one moves the running total. D sits below zero after the total, because it is reported beside it.
beside the total, not in it
| Module | Name | Per unit | Running total | Status |
|---|---|---|---|---|
| A1 | Raw material supply | 242.172 | 242.172 | Declared |
| A2 | Transport to the plant | 0.908795 | 243.081 | Declared |
| A3 | Manufacturing | 21.6635 | 264.744 | Declared |
| A4 | Transport to site | 2.25863 | 267.003 | Declared |
| A5 | Installation | 744.606 | 1,011.61 | Declared |
| B1 | Use | not declared | 1,011.61 | Not declared |
| B2 | Maintenance | not declared | 1,011.61 | Not declared |
| B3 | Repair | not declared | 1,011.61 | Not declared |
| B4 | Replacement | 41.4085 | 1,053.02 | Declared |
| B5 | Refurbishment | not declared | 1,053.02 | Not declared |
| B6 | Energy in use | 3,072.9 | 4,125.92 | Declared |
| B7 | Water in use | not declared | 4,125.92 | Not declared |
| C1 | Demolition | not declared | 4,125.92 | Not declared |
| C2 | Waste transport | 0.299809 | 4,126.22 | Declared |
| C3 | Waste processing | 10.3985 | 4,136.62 | Declared |
| C4 | Disposal | 2.86091 | 4,139.48 | Declared |
| Total | EPD total, declared modules | 4,139.48 | Sum of the declared modules | |
| D | Beyond the system boundary | −256.533 | not added | Beside the total, not in it |
What this number covers
Follow 1 unit of this product through EN 15804's stages. The total counts what the EPD declares; what it leaves out stays visible.
A1-A3Product
Materials and making the product
Included265A4-A5Construction
Delivery and installation
Included747B1-B7Use
The product in service: maintenance, repair, replacement and the energy and water it uses; B1 to B3, B5, B7 not declared
B4, B63,114C1-C4End of life
Waste transport to disposal; C1 not declared
C2 to C413.6DBeyond the boundary
Recovery after end of life
Not in the total−257
Outside this boundary
- Retail
- Recycling credit
The recycling credit is module D, shown beside the total.
Gases
- Fossil CO₂e4,139
- Biogenic CO₂e40.6
- Land-use CO₂e4.75
The total counts fossil CO₂e. EPD Ireland reports biogenic and land-use CO₂e separately; they are shown beside it, not added.
From EPD Ireland's record to a comparable factor
EPD Ireland publishes this EPD with one value per module. Each field as printed, and what open-climate.ai made of it.
The total and its modules
Use a module on its own when you report it in a different year or scope; never add one to the total.
About this factor
From EPD Ireland
What it is
The dataset is representative for the production processes used in 2021. The data Quality Level, according to Table E.1 of EN 15804:2012+A2:2019, Annex E, is as follows: • Geographical representativeness: Very Good • Technical representativeness: Good • Time representativeness: Very Good Allocation of energy and electricity types and amounts to the various manufacturing processes has been provided by the manufacturers along with production waste. Allocation of impacts to the products is based on the product composition mass. Flows related to human activities such as employee transport are excluded. The construction of capital assets such as buildings, manufacture of machines and transportation systems are also excluded since the related flows are assumed to be negligible compared to the manufacture of the building material when compared to these systems over a full lifetime of operation. The cut-off criteria of section 6.3.6 of EN15804:2012+A2:2019 have been followed, where 99% of the total energy and materials are included, and the total neglected input flows for the modules reported on in the LCA are less than 5% of the energy usage and mass.What it includes
Full technical details on these products can be found at: https://www.proair.ie/products/proair-pa600li/Where it applies
The ProAir PA600LI/PA600PLI Heat Recovery Ventilation system is used in residential units, small offices, classrooms, etc. It supplies fresh air and extracts stale air on a continuous basis throughout the building. It is designed to operate continuously at a low rate to minimise the electrical energy consumption. It removes excess moisture from the premises, and prevents the build up of condensation and consequent mould. It has two low energy electrical fans and it operates silently. It uses G4 grade air filters and has touch screen control. It is best placed within the thermal envelope of the building say at high level in a utility room or hot press in order to save on floor space. If this is not an option it may be placed in the attic. Main features: • Heat Recovery Ventilation unit is suitable for residential and small commercial up to 180 - 220m² • Heat Exchanger: Counter-flow pure polyproplene plates • Fans: Two R3G190 Backward curved impellers • Air Handling Unit body: Expanded polyethylene with metal coverings • Air Filters: G4 Pleated panels on supply and extract • Control: 0-10v input variable speed, with timed boost over-ride • Max Airflow: 323 m3/hr @ 100PA The main materials used in the ProAir 600 PLI/LI are: Material: PE foam kg per FU: 4 - 7 Post consumer recycled material (%): 0 Pre-consumer recycled material (%): 0 Material: PVC and PVC fixings kg per FU: 1 - 2 Post consumer recycled material (%): 0 Pre-consumer recycled material (%): 0 Material: Silicone sealant kg per FU: 0.5 - 1.5 Post consumer recycled material (%): 0 Pre-consumer recycled material (%): 0 Material: Galvanised steel kg per FU: 3 - 5 Post consumer recycled material (%): 0 Pre-consumer recycled material (%): 0 Material: Hytdrocarbon sealant kg per FU: 1 - 2 Post consumer recycled material (%): 0 Pre-consumer recycled material (%): 0 Material: Electric motor kg per FU: 2 - 3 Post consumer recycled material (%): 0 Pre-consumer recycled material (%): 0 Material: Steel kg per FU: 0.05 - 0.15 Post consumer recycled material (%): 0 Pre-consumer recycled material (%): 0 Material: Mild steel kg per FU: 0.1 - 0.4 Post consumer recycled material (%): 0 Pre-consumer recycled material (%): 0 Material: Copper kg per FU: 0.1 - 0.2 Post consumer recycled material (%): 0 Pre-consumer recycled material (%): 0 Material: Brass kg per FU: 0.01 - 0.04 Post consumer recycled material (%): 0 Pre-consumer recycled material (%): 0 Material: Aluminium kg per FU: 3 - 5 Post consumer recycled material (%): 0 Pre-consumer recycled material (%): 0 Material: Cardboard kg per FU: 0.1 - 0.4 Post consumer recycled material (%): 0 Pre-consumer recycled material (%): 0 Material: LDPE kg per FU: 0.5 - 0.9 Post consumer recycled material (%): 0 Pre-consumer recycled material (%): 0 Material: PCB kg per FU: 0.2 - 0.5 Post consumer recycled material (%): 0 Pre-consumer recycled material (%): 0 Material: Neoprene kg per FU: 0.1 - 0.2 Post consumer recycled material (%): 0 Pre-consumer recycled material (%): 0 Material: Polycarbonate kg per FU: 0.001 - 0.01 Post consumer recycled material (%): 0 Pre-consumer recycled material (%): 0 Material: PP synthetic fibre kg per FU: 0.1 - 0.3 Post consumer recycled material (%): 0 Pre-consumer recycled material (%): 0 Material: Polypropylene kg per FU: 4.5 - 6 Post consumer recycled material (%): 0 Pre-consumer recycled material (%): 0 Material: Packaging kg per FU: 0 Post consumer recycled material (%): 0 Pre-consumer recycled material (%): 0 The units are delivered to site in company vans. No product packaging is used Component parts are assembled manually on an assembly line. The raw materials of the constituent components mostly comprise: PE, PVC, PP (fibre), neoprene, aluminium, mild steel, galvanised steel, copper, silicone & hydrocarbon sealants, and printed circuit boards. Electricity is used for lighting, heating and power for power tools.Source and licence
- Value
- Summed by open-climate.ai from its parts
- Publisher
- EPD Ireland (Irish Green Building Council)
- Published
- 2 October 2026
- Valid until
- 31 December 2027
The values and their metadata are served in full and may be reused with credit to the publisher.
Cite this factor
EPD Ireland (Irish Green Building Council), EPD data from https://epdireland.lca-data.com. Normalised by open-climate.ai, https://open-climate.ai/factors/libraries/epd_ireland/ (CC BY 4.0). https://open-climate.ai/factors/ef-epdireland-proair_heat_recovery-ie-unit-cradle_to_grave-c53b5516/?v=efv1-7ff43057042b857bf61c001a6d13f499
Something looks wrong?